30kW Natural gas CCHP genset heat calculationHP genset heat calculation

2017-04-05 09:02:43 XINDAXIN

 The following heat was calculated on 30kW combustion engine:

 

I.  CHP data

Gas in air for complete combustion formula:

Gas in air for uncomplete combustion formula:

When 30kW natural gas genset normally running , exhaust gas temperature is around 550℃.

Since methane gas composition are different in every places,to fully combust of fuel, the mixing ratio of gas and air in general is the theoretical value of about 1.4 times.After measured there will be 253.3kg gas produced per hour.

(Fuel gas composition : CO2 13%  H2O 11%  N76%,Specific heat capacity is 0.27kcal/kg·℃ at 100℃~600℃)

Data list

Specific heat capacity

(kcal/kg.℃)

Fuel gas

Air

100℃

0.255

0.241

200℃

0.262

0.245

300℃

0.268

0.250

400℃

0.275

0.255

500℃

0.283

0.261

600℃

0.290

0.266

 

Fuel gas heat recovered for Each gas genset :

253.3kg×0.27 kcal/kg·℃×550℃37,600kcal/h

253.3kg×0.27 kcal/kg·℃×550-160℃26,700kcal/h

 

II. Ammonia absorption refrigeration unit in accordance with a factor of 0.5 to calculate the thermodynamic

Ammonia absorption refrigeration unit cooling capacity can be up to 15,000 kcal / h. According to clients request, cooling water amount is 5.9ton per day, genset will run appro.3 hrs, so 15,000kcal/h*3hrs=45,000kcal;45,000kcal/5,900kg=7.6℃, which means 5.9tons of water can be cooled from 10.6℃ to 3℃ .

Cooling capacity is related to heat amount .